Commissioning
6.5 Local commissioning
SITRANS LT500 with ultrasonic transducer inputs
84 Compact Operating Instructions, 02/2024, A5E52021877-AA
Step: Pump control mode
Pump control mode
Sets the control algorithm used to activate the relay.
Setting
Alternate duty assist
Alternate duty backup
Service ratio duty assist
Service ratio duty backup
Fixed duty assist
Fixed duty backup
Default
Alternate duty assist
This step is only visible if previous step "Number of pumps" is set to a value greater than one.
Step: Pump control
Note
Step is repeated per pump
The parameters in this step will need to be set for each pump used in the application.
Pump 1
Sets relay assigned to pump.
Setting
Relay output 1
Relay output 2
Relay output 3
Relay output 4
Relay output 5
Relay output 6
Default
Not applicable