Page 8 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270
mmmmm
Operation - PDM
3. After opening object in SIMATIC PDM, set the product capabilities when prompted.
If you do not know the model connected, click on Read Product Capabilities from
Device, and the model will be automatically selected.
This setting decides what parameters are visible from the PDM menus.
4. Open the menu Device – Master Reset and click on OK to perform a reset to Factory
Defaults.
5. After the reset is complete upload parameters to the PC/PG.
6. Configure the device via the Quick Start Wizard for your application.
Quick Start Wizard steps
Open the Device menu in SIMATIC PDM and select the Quick Start applicable to your
application:
Notes:
The Quick Start wizard settings are inter-related and changes apply only after you
click on Apply and Transfer at the end of the final step.
Initial Quick Start parameter values are not default values and do not necessarily
reflect the current device configuration.
The format of date fields in PDM will reflect the user’s operating system
configuration.
Click on BACK to return and revise setting or Cancel to exit the Quick Start.