Page 22 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270
mmmmm
Operation - PDM
Pump Control Wizard
The Pump Control Setup Wizard provides an easy step-by-step guide to help you
configure the pumps and relays for a simple application.
Pump Control Wizard steps
Launch SIMATIC PDM, open the menu Device – Wizard - Pump Control, and follow steps.
Step 1 – Application
1) Enable pump control, and select which relay is wired to Pump 1. (The relay for Pump
2 will be set automatically based on your selection for Pump 1.)
2. Click on Next.
Notes:
Complete the appropriate Quick Start Wizard (Level, Volume, or Volume
Linearization) prior to programming pump control.
The Pump Control Setup Wizard settings are inter-related and changes apply only
after you click on Apply and Transfer at the end of the final step.
Initial Pump Control Wizard parameter values are not default values and do not
necessarily reflect the current device configuration.
Click on BACK to return and revise setting or Cancel to exit the Pump Control Wizard.