Page 60 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270
mmmmm
Operation - AMS
Wizard - Quick Start (Volume - Linearization)
Step 1 – Identification
1) Navigate to Configure/Setup > Wizard > Wizard - Quick Start (Volume -
Linearization).
2) You can accept the default values without modification. (TAG, Long TAG, Descriptor,
Message, and Date fields can be left blank.) If desired, make changes then click on
Next.
Step 2 – Application
1. Select the Siemens transducer connected to the device.
2. The Application Type defaults to Volume.
1
3. Select the Temperature Source, and if fixed, enter a Fixed Temperature value.
4. Click on Next.
1.
For details see parameter
2.1.3.Sensor Mode
in SITRANS LUT400 (HART) Operating
Instructions (7ML19985MV01).