General Operation
7.7 Pump Control
SITRANS LUT400
Operating Instructions, 07/2019, A5E33329501-AC
107
7.7.3.2 Set Relays to FIXED DUTY ASSIST (FDA)
Pump Control
Mode (2.7.1.5.)
FDA Sets the control algorithm used to trip the pump relay to
. Only one pump can run at a time.
Set the ON Setpoints
ON Setpoint Pump 1
1.3 m Sets the level at which pump 1 turns on.
ON Setpoint Pump 2
1.2 m Sets the level at which pump 2 turns on.
Set the OFF Setpoints
OFF Setpoint Pump 1
0.4 m Sets the level at which pump 1 turns off.
OFF Setpoint Pump 2
0.3 m Sets the level at which pump 2 turns off.
7.7.3.3 Set Relays to FIXED DUTY BACKUP (FDB)
Pump Control
Mode (2.7.1.5.)
FDB Sets the control algorithm used to trip the pump relay to
. Only one pump can run at a time.
Set the ON Setpoints
ON Setpoint Pump 1
1.3 m Sets the level at which pump 1 turns on.
ON Setpoint Pump 2
1.2 m Sets the level at which pump 2 turns on.