General Operation
7.7 Pump Control
SITRANS LUT400
Operating Instructions, 07/2019, A5E33329501-AC
113
7.7.6 Other Pump Controls
Prerequisite: Common parameters must first be set for each pump control below:
Parameter
Description
Sensor Mode (2.1.2.) (Page 168) or Sensor Mode (2.1.3.) (Page 169)
Volume
Response rate in Quick Start (Page 59)
Medium
Transducer (2.1.6.) (Page 170)
XPS-10
Units (2.1.1.) (Page 168) M
Low Calibration Point (2.2.1.) (Page 171)
1.8
High Calibration Point (2.2.2.) (Page 172)
0.4
7.7.6.1 Totalizing pumped volume
Available only on LUT430 (Pump and Flow model), and LUT440 (OCM model).
Prerequisite: The volume of the vessel must be known.
Parameter
Sample Value
Description
Vessel Shape (2.6.1.)
(Page 180)
LINEAR Vessel shape is linear (flat bottom)
Maximum Volume (2.6.3.)
(Page 182)
17.6 Max volume is 17.6m
3
or 17,600 liters.
Pump Control Mode (2.7.1.4.)
(Page 185) or Pump Control
Mode (2.7.1.5.) (Page 185)
ADA Sets the control algorithm used to trip the pump
relay to
ALTERNATE DUTY ASSIST
.
ON Setpoint Pump 1 (2.7.1.6.)
(Page 186)
1.0 m Sets the level at which pump 1 turns on. The
first cycle will use this setpoint. Subsequent
cycles rotate the setpoint among the pumps.
ON Setpoint Pump 2 (2.7.1.8.)
(Page 186)
1.2 m Sets the level at which pump 2 turns on.
OFF Setpoint Pump 1 (2.7.1.7.)
(Page 186)
0.2 m Sets the level at which pump 1 turns off. The
first cycle will use this setpoint. Subsequent
cycles rotate the setpoint among the pumps.
OFF Setpoint Pump 2 (2.7.1.9.)
(Page 186)
0.3 m Sets the level at which pump 2 turns off.
Totalizer Decimal Position
(2.7.3.2.) (Page 195)
2 DIGITS Sets the totalizer display to 2 digits.
Totalizer Multiplier (2.7.3.3.)
(Page 195)
1000 Actual volume is divided by 1000, prior to dis-
play on LCD.
Inflow/Discharge Adjust
(2.7.3.4.) (Page 195)
RATE
ESTIMATE
The inflow rate measured just prior to the start
of the pump cycle is used to estimate the inflow
for the duration of the cycle.
1. Display vessel volume on the LCD (set parameter Sensor Mode (2.1.2.) (Page 168) to
VOLUME).
2. Toggle to SV on LCD to display current level (set parameter Sensor Mode Secondary
(2.1.4.) (Page 170) to LEVEL).
3. See Running Totalizer (2.7.3.1.) (Page 194) to view pumped volume.