SITRANS LUT400
Operating Instructions, 07/2019, A5E33329501-AC
175
9.2.4 Fail-Safe (2.4.)
The fail-safe parameters ensure that the devices controlled by the SITRANS LUT400 default
to an appropriate state when a valid level reading is not available. The PV region on LUI will
display dashes (– – – – – – –) until the fail-safe fault has been cleared. (See General Fault
Codes (Page 269) for a list of faults that will cause failsafe.)
Note
When a Loss of Echo occurs
Material Level (2.4.1.) (Page 175
) determines the material level
to be reported when the Fail
-safe timer expires. See Loss of Echo (LOE) (Page 298) for
9.2.4.1 Material Level (2.4.1.)
Note
The default is a factory setting and depends whether or not your device was ordered as
NAMUR NE43
-compliant for Fail-safe.
Defines the mA output to use (shown in Current Output Value (2.5.8.) (Page 179)) when the
Failsafe Timer expires and the device is still in an error condition.
VALUE User-selected value [defined in Fail-Safe mA Value (2.4.3.)
(Page 175): default 3.58 mA]
VALUE (if ordered with NAMUR NE43 compliant fail-safe preset)
HOLD (if ordered without NAMUR NE43 compliant fail-safe preset)
9.2.4.2 LOE Timer (2.4.2.)
Sets the time to elapse since the last valid reading, before the Fail-safe Material Level is
reported (defined in seconds).
9.2.4.3 Fail-Safe mA Value (2.4.3.)
Note
Material Level (2.4.1.)
(Page 175) must be set to
for the Material Level (2.4.1.)
e 175) value to be reported.
Allows the user to define the mA value to be reported when the Fail-safe timer expires.