SITRANS LUT400
178 Operating Instructions, 07/2019, A5E33329501-AC
9.2.5.3 4 mA Setpoint (2.5.3.)
Sets the process level corresponding to the 4 mA value. 4 mA always defaults to 0 m, and
Current Output Function (2.5.1.) (Page 176) determines the type of measurement. [See
Current Output Function (2.5.1.) (Page 176) for an illustration.]
Range: Level, Space, Distance,
Head: 0.000 to 60.000 m
Volume: 0.0 to Max. Volume
Default:
(set to value corresponding to 0% as defined by Current Output Function
● Enter the reading that is to correspond to a 4 mA output.
● Units are defined in Units (2.1.1.) (Page 168) for Level, Space, Distance, or Head, and in
Flowrate Units (2.15.3.7.) (Page 233) for Flow. Volume units are converted from a level
value.
9.2.5.4 20 mA Setpoint (2.5.4.)
Sets the process level corresponding to the 20 mA value. 20 mA always defaults to 60 m,
and
Current Output Function (2.5.1.) (Page 176) determines the type of measurement. [See
Current Output Function (2.5.1.) (Page 176) for an illustration.]
Range: Level, Space, Distance,
Head: 0.000 to 60.000 m
Volume: 0.0 to Max. Volume
Default: Level, Space, Distance,
Head:
Volume:
Flow:
(set to value corresponding to 100% as defined by Current Output Function and
● Enter the reading that is to correspond to a 20 mA output.
● Units are defined in Units (2.1.1.) (Page 168) for Level, Space, or Distance, or Head, and
in Flowrate Units (2.15.3.7.) (Page 233) for Flow. Volume units are converted from a level
value.
9.2.5.5 Minimum mA Limit (2.5.5.)
Prevents the mA output from dropping below this minimum level for a measurement value.
This does not restrict the Fail-safe or Manual settings.