Enter up to 32 level breakpoints, where the corresponding volume is known. The values
corresponding to 0% and 100% levels must be entered, and breakpoints can be ordered
from top to bottom, or the reverse.
Breakpoints are grouped into four tables: Table 1-8, Table 9-16, Table 17-24, and Table 25-
32.
Entering breakpoints via SIMATIC PDM:
● See Using Linearization via the Quick Start wizard in the LUT400 Communications
manual
1
.
Entering breakpoints via the local push buttons:
1. The default unit for level values is m: to change it navigate to Setup (2.) (Page 168) >
Sensor (2.1) (Page 168) > Units (2.1.1.) (Page 168) , and select the desired unit.
2. Navigate to Setup (2.) (Page 168) > Volume (2.6.) (Page 179
) > Table 1-8 (2.6.7.), and
enter the value.
3. Go to the appropriate table for the particular breakpoint you wish to adjust: for example,
go to Table 1-8 for breakpoint 1.
4. Under Table 1-8, go to Level 1 (2.6.7.1.) (Page 183) to enter the level value for the
breakpoint 1.
5. Under Table 1-8, go to Volume 1 (2.6.7.2.) (Page 183) to enter the volume value for the
breakpoint 1.
6. Repeat steps 3 to 5, until values have been entered for all required breakpoints.
1)
Communications for SITRANS LUT400 (HART) Manual (7ML19985NE01)
Level 1 (2.6.7.1.)
1. Press RIGHT arrow to open Edit mode.
2. Enter level value and press RIGHT arrow to accept it.
3. Press Down ARROW to move to corresponding volume breakpoint.
Volume 1 (2.6.7.2.)
1. Press RIGHT arrow to open Edit mode.
2. Enter volume value and press RIGHT arrow to accept it.
3. Press Down ARROW to move to next level breakpoint.