SITRANS LUT400
186 Operating Instructions, 07/2019, A5E33329501-AC
1)
Option available only on LUT430, LUT440.
Each algorithm defines a pump duty and pump start method.
ON Setpoint Pump 1 (2.7.1.6.)
The level at which Pump 1 turns ON, defined in Units (2.1.1.) (Page 168).
Range: 0.000 to 99999.000
This parameter is set according to level even when another reading, such as volume, is
shown on the LCD.
OFF Setpoint Pump 1 (2.7.1.7.)
The level at which Pump 1 turns OFF, defined in Units (2.1.1.) (Page 168).
Range: 0.000 to 99999.000
This parameter is set according to level even when another reading, such as volume, is
shown on the LCD.
ON Setpoint Pump 2 (2.7.1.8.)
The level at which Pump 2 turns ON, defined in Units (2.1.1.) (Page 168).
Range: 0.000 to 99999.000
This parameter is set according to level even when another reading, such as volume, is
shown on the LCD.
OFF Setpoint Pump 2 (2.7.1.9.)
The level at which Pump 2 turns OFF, defined in Units (2.1.1.) (Page 168).
Range: 0.000 to 99999.000
This parameter is set according to level even when another reading, such as volume, is
shown on the LCD.