EasyManua.ls Logo

Siemens SITRANS LUT400 - Page 197

Siemens SITRANS LUT400
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SITRANS LUT400
Operating Instructions, 07/2019, A5E33329501-AC
195
Totalizer Decimal Position (2.7.3.2.)
Sets the maximum number of decimal places to be displayed on the LCD.
Options
NO DIGITS
No digits after the decimal position
1 DIGIT
1 digit after the decimal point
*
2 DIGITS
2 digit after the decimal point
3 DIGITS 3 digit after the decimal point
Totalizer Multiplier (2.7.3.3.)
Use this feature if the LCD Total increments by an amount that is too large (or too small).
Options
.001
.01
.1
*
1
10
100
1000
10,000
100,000
1,000,000
10,000,000
Enter the factor by which actual volume is divided, prior to display on LCD. Use a value such
that the nine-digit totalizer doesn’t roll over between readings.
Example:
For an LCD Total display in 1000s of volume units, enter 1000. In this example, 10,000
volume units would display as
10.
Inflow/Discharge Adjust (2.7.3.4.)
Determines how inflow (or discharge) adjustment is made.
Options
* BASED ON RATE
ESTIMATION
The inflow rate measured just prior to the start of the pump
cycle is used to estimate the inflow for the duration of the
cycle.
BASED ON PUMP
CYCLE
The inflow is calculated using the change of volume between
the end of the last pump cycle and the start of the next one,
and the time period between the last cycle and the current
one.
NO ADJUSTMENT
No inflow adjustment is made (assumes an inflow of zero).
For an illustration, see Pump Totalizers (Page 301).

Table of Contents

Other manuals for Siemens SITRANS LUT400

Related product manuals