SITRANS LUT400
196 Operating Instructions, 07/2019, A5E33329501-AC
Reset Running Totalizer (2.7.3.5.)
Select YES to reset pumped volume totalizer value to zero.
9.2.8 Alarms (2.8.)
The SITRANS LUT400 supports eight alarm types. Any alarm can be assigned to any
available relay.
It is possible to assign more than one alarm to the same relay. In this case, the relay will
activate if any one of the alarms is activated. If no alarms are activated, the relay will become
inactive.
For details on relay behaviour under fail-safe conditions, see Alarm relays (Page 87).
Note
Default settings in the paramete
r tables are indicated with an asterisk (*) unless explicitly
9.2.8.1 High Level Alarm (2.8.1.)
Reported when material level is within a user-defined range (see High Level Value ON
(2.8.1.2) (Page 196) and High Level Value OFF (2.8.1.3) (Page 197)).
Can be used in conjunction with Time To Spill (2.8.12.) (Page 207).
Enable (2.8.1.1)
Enables/disables High Level Alarm.
High Level Value ON (2.8.1.2)
Sets the material level (defined in Units (2.1.1.) (Page 168)) at which the High Level Alarm
will activate.
Range: 0.000 to 99999.000
Value must be lower than Level To Spill (2.8.12.1.) (Page 207) if Time to Spill feature is
used.