Enable (2.8.7.1.)
Enables/disables High Temperature Alarm.
High Temperature Value ON (2.8.7.2.)
Sets the temperature value (defined in ° C) at which the High Temperature Alarm will
activate.
Range: -273.0 to +273.0 °C (-459.0 to +523.0 °F)
High Temperature Value OFF (2.8.7.3.)
Sets the temperature value (defined in ° C) at which the High Temperature Alarm will de-
activate.
Range: -273.0 to +273.0 °C (-459.0 to +523.0 °F)
Assigned Relay (2.8.7.4.)
Determines which relay (if any) will be activated when the High Temperature Alarm
activates.
Alarm State (2.8.7.5.)
Read only. Used to view the current state of the High Temperature Alarm.
9.2.8.8 Fail-safe Fault Alarm (2.8.8.)
Reported when fault that has caused a fail-safe condition is present.