SITRANS LUT400
Operating Instructions, 07/2019, A5E33329501-AC
205
High Flowrate Value OFF (2.8.9.3.)
Sets the flowrate value (defined in Flowrate Units (2.15.3.7.) (Page 233)) at which the High
Flowrate Alarm will de-activate.
Values
Range: 0.000 to 99999.000
Default: 0.000
Assigned Relay (2.8.9.4.)
Determines which relay (if any) will be activated when the High Flowrate Alarm activates.
Options
*
NO RELAY
RELAY 1
RELAY 2
RELAY 3
Alarm State (2.8.9.5.)
Read only. Used to view the current state of the High Flowrate Alarm.
Options
ACTIVE
INACTIVE
9.2.8.10 Low Flowrate Alarm (2.8.10.)
Available only on LUT440 (OCM model).
Reported when the OCM flowrate is within a user-defined range (see Low Flowrate Value
ON (2.8.10.2.) (Page 205) and Low Flowrate Value OFF (2.8.10.3.) (Page 206)).
Enable (2.8.10.1.)
Enables/disables Low Flowrate Alarm.
Options
ENABLED
*
DISABLED
Low Flowrate Value ON (2.8.10.2.)
Sets the flowrate value (defined in Flowrate Units (2.15.3.7.) (Page 233)) at which the Low
Flowrate Alarm will activate.
Values
Range: 0.000 to 99999.000
Default: 0.000