SITRANS LUT400
Operating Instructions, 07/2019, A5E33329501-AC
205
High Flowrate Value OFF (2.8.9.3.)
Sets the flowrate value (defined in Flowrate Units (2.15.3.7.) (Page 233)) at which the High
Flowrate Alarm will de-activate.
Range: 0.000 to 99999.000
Assigned Relay (2.8.9.4.)
Determines which relay (if any) will be activated when the High Flowrate Alarm activates.
RELAY 2
Alarm State (2.8.9.5.)
Read only. Used to view the current state of the High Flowrate Alarm.
9.2.8.10 Low Flowrate Alarm (2.8.10.)
Available only on LUT440 (OCM model).
Reported when the OCM flowrate is within a user-defined range (see Low Flowrate Value
ON (2.8.10.2.) (Page 205) and Low Flowrate Value OFF (2.8.10.3.) (Page 206)).
Enable (2.8.10.1.)
Enables/disables Low Flowrate Alarm.
Low Flowrate Value ON (2.8.10.2.)
Sets the flowrate value (defined in Flowrate Units (2.15.3.7.) (Page 233)) at which the Low
Flowrate Alarm will activate.
Range: 0.000 to 99999.000