SITRANS LUT400
216 Operating Instructions, 07/2019, A5E33329501-AC
Relay Duration (2.11.3.3.)
The time in seconds from one change of state in the relay to the next.
Values
Range: 0.1 to 1024.0
Default: 0.2
Assigned Relay (2.11.3.4.)
Determines the relay assigned to external totalizer control.
Options
*
RELAY 1
RELAY 2
RELAY 3
Relay Logic (2.11.3.5.)
Use to change the behaviour of the relay assigned to external totalizer control.
Options
*
NORMALLY OPEN
NORMALLY CLOSED
Relay contact operation is NORMALLY CLOSED for alarms and NORMALLY OPEN for
controls.
By default a control contact is Normally Open. For Relay Duration (2.11.3.3.) (Page 216) the
corresponding relay coil is energized. By setting this parameter to
Normally Closed, the relay
coil will be de-energized for the duration phase.
9.2.11.4 External Sampler (2.11.4.)
Available only on LUT430 (Pump and Flow model), and LUT440 (OCM model).
This function uses a relay to signal a flow sampling device when a certain volume of material
has passed through a system (set by the Multiplier), or after a defined period of time (set by
the Interval). The relay toggles on and off at a rate set by the parameters below. (For details
on relay behaviour under fail-safe conditions, see Miscellaneous relays (Page 88).)
Note
Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly
stated.
Enable (2.11.4.1.)
Enables/disables flow sampler relay control.
Options
ENABLED
*
DISABLED