SITRANS LUT400
248 Operating Instructions, 07/2019, A5E33329501-AC
Reminder Activation (3.3.3.4.)
Note
To modify this parameter via SIMATIC PDM it must be accessed via the pull
-down menu
– Maintenance.
Allows you to enable a maintenance reminder.
REMINDER 1 (MAINTENANCE REQUIRED)
REMINDER 2 (MAINTENANCE DEMANDED)
1. First set the values in Reminder 1 before Lifetime (Required) (3.3.3.5.)
(Page 248)/Reminder 2 before Lifetime (Demanded) (3.3.3.6.) (Page 248).
2. Select the desired Reminder Activation option.
Reminder 1 before Lifetime (Required) (3.3.3.5.)
If Remaining Lifetime (3.3.3.3.) (Page 247) is equal to or less than this value, the device
generates a Maintenance Required reminder.
Range: 0.000 to 20.000 years
Default: 0.164 years (8 weeks)
1. Modify values as required.
2. Set Reminder Activation (3.3.3.4.) (Page 248) to the desired option.
Reminder 2 before Lifetime (Demanded) (3.3.3.6.)
If Remaining Lifetime (3.3.3.3.) (Page 247) is equal to or less than this value, the device
generates a Maintenance Demanded reminder.
Range: 0.000 to 20.000 years
Default: 0.019 years (1 week)
1. Modify values as required.
2. Set Reminder Activation (3.3.3.4.) (Page 248) to the desired option.
Maintenance Status (3.3.3.7.)
Indicates which level of maintenance reminder is active.
In SIMATIC PDM, open the menu View – Device Status, click on the Maintenance tab, and
check the Device Lifetime Status window.