SITRANS LUT400
260 Operating Instructions, 07/2019, A5E33329501-AC
9.4 Communication (4.)
9.4.1 Device Address (4.1.)
Sets the device address or poll ID on a HART network.
Values
Range: 0 to 63 (Set within range of 0 to 15 if HART 5 master used.)
Default: 0
To reset Device Address via SIMATIC PDM:
Open the project in Process Device Network View then right-click on the device.
Go to Object Properties and open the Connection tab to access the field Short Address.
Note
The following list of parameters are available in PDM. Unless otherwise stated, the options
are displayed in integer format (as requir
ed by HART communications).
Manufacturer’s ID
Read only. Numerical code that refers to the manufacturer of the device (e.g. 42, which
refers to Siemens).
Device Id
Read only. Unique identification of the device by manufacturer and device type.
Product Id
Read only. Unique identification of the product by model number.
Device Revision
Read only. Device revision associated with a specific EDD.
EDD Revision
Read only. Revision of a specific EDD associated with the device.
Universal Command Revision
Read only. Revision of the Universal Device Description associated with the device.
Protocol
Read only. The communication protocol supported by the device.
Common Practice Command Revision
Read only. Revision of the set of HART common practice commands supported by the
device.
Configuration Change Counter
Read only. Indicates the number of times the device’s configuration or calibration has been
changed by a host application or from a local operator interface.