EasyManua.ls Logo

Siemens SITRANS LUT400 - Page 272

Siemens SITRANS LUT400
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SITRANS LUT400
270 Operating Instructions, 07/2019, A5E33329501-AC
General Fault Codes
Code / LUI
Icon
Code /
PDM Icon
Meaning
Corrective Action
0
0
* Loss of echo (LOE).
The device was unable to get a
measurement within the Fail-safe
LOE Timer period. Possible
causes: faulty installation, foam-
ing/other adverse process condi-
tions, invalid calibration range.
Ensure installation details are
correct.
Adjust process conditions to
minimize adverse conditions.
Correct range calibration.
If fault persists, contact your
local Siemens representative.
1
1
* Cable fault.
Broken cable.
Inspect attached cabling and any
termination points to ensure no
disconnection or damage; re-
pair/replace if necessary. If no
issue with cabling, contact your
local Siemens representative.
3
3
Device is nearing its lifetime limit
according to the value set in
Maintenance Required Limit.
Replacement is recommended.
4
4
Device is nearing its lifetime limit
according to the value set in
Maintenance Demanded Limit.
Replacement is recommended.
5
Saving Parameters.
(LUI fault only.) Saving is in pro-
gress. Do not turn off the device.
Wait for completion.
6
6
Sensor is nearing its lifetime limit
according to the value set in
Maintenance Required Limit.
Replacement is recommended.
7
7
Sensor is nearing its lifetime limit
according to the value set in
Maintenance Demanded Limit.
Replacement is recommended.
8
8
Service interval as defined in
Maintenance Required Limit has
expired.
Perform service.
9
9
Service interval as defined in
Maintenance Demanded Limit
has expired.
Perform service.