EasyManua.ls Logo

Siemens SITRANS LUT400 - Interface

Siemens SITRANS LUT400
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SITRANS LUT400
Operating Instructions, 07/2019, A5E33329501-AC
285
12.3 Interface
Outputs
mA analog
4-20 mA
1)
600 ohms maximum in ACTIVE mode, 750 ohms maximum in PASSIVE mode
Resolution of 0.1%
Isolated
Relays
2)
(3)
2 control
1 alarm control
Control relays
2 Form A (SPST), NO relays
Rated 5A at 250 V AC, non-inductive
Rated 3A at 30 V DC
Alarm relay
1 Form C (SPDT), NO or NC relay
Rated 1A at 250 V AC, non-inductive
Rated 3A at 30 V DC
Inputs
Discrete (2)
0-50 V DC maximum switching level
Logical 0 = < 10 V DC
Logical 1 = 10 to 50 V DC
3 mA maximum draw
Programming
Primary
Local push buttons
Secondary
PC running SIMATIC PDM
PC running Emerson AMS Device Manager
PC running a web browser
PC running a Field Device Tool (FDT)
Field Communicator 375/475 (FC375/FC475)
Compatible transducers
EchoMax series and STH series
Transducer frequency
10 to 52 kHz
Communication
HART 7.0
USB

Table of Contents

Other manuals for Siemens SITRANS LUT400

Related product manuals