SITRANS LUT400
286 Operating Instructions, 07/2019, A5E33329501-AC
• Back-lit LCD
• Dimensions: –60 x 40 mm (2.36 x 1.57")
• Resolution: –240 x 160 pixels
• Removable display, operational up to 5 m from enclosure base
1)
Device may output a high current reading when power is applied or removed.
2)
All relays are certified only for use with equipment that fails in a state at or under the rated
maximums of the relays.
12.4 Mechanical
• 144 mm (5.7") x 144 mm (5.7") x 146 mm (5.75")
• IP65 / Type 4X / NEMA 4X
• Polycarbonate
• 144 mm (5.7") x 144 mm (5.7") x 22 mm (0.87")
• IP65 / Type 3 / NEMA 3
• Polycarbonate
• Operational up to 5 m from enclosure base
Blank lid
• 144 mm (5.7") x 144 mm (5.7") x 22 mm (0.87")
• IP65 / Type 4X / NEMA 4X
• Polycarbonate
Ingress protection reduced
• Ingress protection of the enclosure is reduced to IP20, and Type 4X / NEMA 4X rating is
void when cable entry knock-out in the blank lid is removed.
• An enclosure reduced to an IP20 rating and intended for use in nonhazardous locations
must be installed in an indoor location free of dust and moisture, or be installed in a
suitably rated field enclosure IP54 or better.
• 190 mm (7.5") x 190 mm (7.5") x 9 mm (0.35")
• Polycarbonate
• Enclosure with display lid: 1.3 kg (2.87 lbs)
• Enclosure with blank lid: 1.2 kg (2.65 lbs)