5.1 Connecting SITRANS LUT400
SITRANS LUT400
Operating Instructions, 07/2019, A5E33329501-AC
45
Synchronizing with another SITRANS LUT400, or other Siemens devices
Other Siemens devices that can be synchronized with the SITRANS LUT400:
DPL+, SPL, XPL+, LU01, LU02, LU10, LUC500, DPS300, HydroRanger 200, HydroRanger
Plus, EnviroRanger, MiniRanger, MultiRanger 100/200
Mount the level monitors together in one cabinet.
Use a common power (mains) supply and ground (earth) for all devices.
Interconnect the SYNC terminals of all level monitors.
Up to 16 Siemens devices can be synchronized together.
For more information or assistance, contact Siemens or your local distributor. Go to:
www.siemens.com/processautomation (www.siemens.com/processautomation
).
5.1.9 Discrete inputs
The SITRANS LUT400 has a 24V power bias (terminal 10) for use with the discrete inputs,
or the discrete inputs can be wired using external power.
Common Neg. for DIs
Pos. Input for DI1
Pos. Input for DI2
Bias supply for Pos. DIs
(ground to terminal 6)
Discrete Inputs used with internal bias supply