Commissioning
6.3 Quick Start Wizards
SITRANS LUT400
66 Operating Instructions, 07/2019, A5E33329501-AC
Response Rate
Sets the reaction speed of the device to measurement changes in the target range.
Response Rate can only be set through the Quick Start Wizard, and any changes made
to
Fill Rate per Minute (2.3.1.) (Page 174), Empty Rate per Minute (2.3.2.) (Page 174
Damping Filter (2.3.3.) (Page 174) parameters following the completion of the wizard will
supersede the Response Rate setting.
Response Rate always displays in m/minute.
Default: SLOW (0.1 m/min)
Use a setting just faster than the maximum filling or emptying rate (whichever is greater).
Slower settings provide higher accuracy, faster settings allow for more rapid level
fluctuations.
Dimension A
The height of the vessel bottom when the bottom is conical, pyramidal, parabolic, spherical,
or flat -sloped.
Dimension L
Length of the cylindrical section of a horizontal parabolic end vessel.
Volume Units
Determines volume measurement units.
L, USGAL, IMPGAL, CUM, USER DEFINED *
* If USER DEFINED option selected, the value must be set after completing the wizard. See
User Defined Unit (2.6.6.) (Page 182).