Commissioning
6.3 Quick Start Wizards
SITRANS LUT400
74 Operating Instructions, 07/2019, A5E33329501-AC
End of QS Volume Wizard
For QS to be successful, all changes must be applied.
BACK, CANCEL, FINISH
(Display returns to 1.1 Quick Start menu when Quick Start is successfully completed or
cancelled. If CANCEL is selected, no changes are written to the device.)
To transfer Quick Start values to the device and return to Program menu, press DOWN
arrow
(Finish). Then press LEFT arrow three times to return to Measurement mode.
ecommended that an Auto Zero Head be performed after completion of the
wizard to ensure best accuracy. See
Auto Zero Head (2.15.2.) (Page 230).
6.3.1.4 Pump Control
Use this wizard to configure pumps if they will be used in your application. Be sure to first
complete the applicable Quick Start Wizard.
1. Press RIGHT arrow
to activate PROGRAM mode and open menu level 1: MAIN
MENU.
2. Press RIGHT arrow
two times to navigate to menu item 1.1.
3. Press RIGHT arrow
to open QS Level.
4. At each step, press DOWN arrow
to accept default values and move directly to the
next item, or RIGHT arrow
to open Edit mode: the current selection is highlighted.
5. Scroll to desired item and press RIGHT arrow
to store the change, then press DOWN
arrow
to continue.
6. At any time, you can press UP arrow
to go back, or LEFT arrow to cancel the
wizard.
Start of Wizard - Pump Control
Note
The introduction screen is
displayed only on the device when using the local push buttons.
This screen is not part of the Quick Start when using SIMATIC PDM.
Shows the type of Wizard to be executed.