Commissioning
6.8 Application examples
SITRANS LUT400
Operating Instructions, 07/2019, A5E33329501-AC
81
Initial Device Setup
Transducer XRS-5 For best accuracy, an XRS-5 transducer should be
used in conjunction with the High Accuracy
SITRANS LUT440.
Temperature Source TS-3 For best accuracy, a TS-3 external temperature
Primary Measuring Device
Exponential Parshall Flumes are a type of exponential device.
Available from the PMD supplier data sheet.
Units corresponding to the head measurement.
Low Calibration Point 1.6 The distance to the empty point or bottom of the
flume. This sets the 4 mA setpoint.
High Calibration Point 1.0 The distance to the Max. Head. This sets the 20 mA
Response Rate Medium(1.0
m/min)
Response rate is set to be faster than the fastest
rise in material level under typical operating condi-
tions. In this example, the rate is faster than the
Peak Time rate provided by the end user.
Method of Flow Calculation
Ratiometric Used when the Max. Head and Max. Flow values
Available from the PMD supplier data sheet.
Set per end user requirements.
Available from the PMD supplier data sheet.
Flowrate Decimal No Digits For the purpose of this example, decimals are not
Low Flow Cutoff 0.00 This parameter stops the LUT440 from totalizing if
the head value corresponding to low flow is
reached. This prevents flow from being totalized
when the head level reaches the ineffective point of
the PMD. Refer to the PMD data sheets for ratings.
Continue with alarm setup below.