General Operation
7.5 Volume
SITRANS LUT400
96 Operating Instructions, 07/2019, A5E33329501-AC
Example:
To configure volume for a vessel with a half-sphere bottom, set the following:
Vessel Shape (2.6.1.)
HALF SPHERE
selects the correct vessel shape
Maximum Volume
100 sets maximum volume at 100 (defined in Vol-
ume Units (2.6.2.) (Page 181))
Dimension A (2.6.4.)
1.3 sets dimension A to 1.3 m
The default reading changes to a range from 0 to 100
The process empty value is still measured to the bottom of the vessel (Low Calibration
Point (2.2.1.) (Page 171) plus any Far Range (2.2.5.) (Page 172
)), not the top of
.