EasyManua.ls Logo

Siemens SITRANS LUT400 - Characterization Chart; Example Chart (with 15 of Possible 32 Level and Volume Breakpoints Defined)

Siemens SITRANS LUT400
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
General Operation
7.5 Volume
SITRANS LUT400
Operating Instructions, 07/2019, A5E33329501-AC
97
7.5.3 Characterization chart
If you cannot use a pre-defined vessel, then use one of the universal vessel shapes and
program the characterization curve.
1. Plot a volume to height chart. Usually a vessel supplier will provide this chart. However, if
you have a custom-built vessel, then you will need access to complete drawings of the
well or accurate measurements.
2. Enter the curve values from this chart into level and volume breakpoint tables (see Table
1-8 (2.6.7.) (Page 182)).
Note
If
breakpoints are entered via LUI, then an upload is performed via PDM, a second
upload through PDM may be necessary to transfer the breakpoint values.
3. Ensure extra points are added around sharp transitions in the vessel volume (for
example: steps in a well wall).
Note
The end points in the curve are 0,0 (fixed) and the point defined by Maximum Level and
Maximum Volume.
7.5.3.1 Example chart (with 15 of possible 32 Level and Volume breakpoints defined):