Sensor coil terminals Terminal type
85 and 86 "e"
Power supply:
Parameter MAG 6000 I Ex de
Supply 115 to 230 VAC or 18 to 30 VDC
Max. allowable supply voltage U
m
(according to
ATEX certificate)
264 V
Ambient temperature -20 to +60 °C (-4 to 140 °F)
Enclosure IP67 / NEMA 4X
WARNING
Fail-safe protection
With intrinsically safe circuits, use only certified meters appropriate for the transmitter.
If a non-conforming suuply unit is used, the "fail-safe" type of protection wil no longer be
effective and the approval certification will be invalid.
User I/O interface
Remote MAG 6000 I: Model 7ME693-2BA4/5
Compact:
MAG 6000 I with MAG 3100 series: Model 7ME63x0-xxxxx-xD/E
Passive current
(31, 32)
Active current
(31, 32)
Relay
(44, 45, 46)
Frequency/pulse
(56, 57)
Profi (FISCO)
(95, 96)
Digital input
(77, 78)
IIC IIB IIC IIC IIC IIC IIC
U
i
28 V DC U
O
30 V DC 30 V DC U
i
30 V DC U
i
28 V DC U
i
17.5 V DC U
i
30 V DC
I
I
100 mA I
O
87.8 mA 87.8 mA I
I
200 mA I
I
100 mA I
I
380 mA I
I
C
I
19.7 nF C
O
557 nF 63 nF C
I
3.3 nF C
I
14.2 nF C
I
0 nF C
I
0 nF
L
I
36 µH L
O
18.4 mH 4.6 mH L
I
0 µH L
I
36 µH L
I
0 µH L
I
0 µH
P
I
0.7 W P
O
0.66 W 0.61 W P
I
1.2 W P
I
1.2 W P
I
5.32 W P
I
1.2 W
Safety notes
2.3 Installation in hazardous area
SITRANS MAG 6000 I/6000 I Ex de
Operating Instructions, 08/2018, A5E02083319-AH
15

Table of Contents