SITRANS P220 (7MF1567)
A5E03304437-02, 12/2011
Dimension drawings of the electrical connections Dimension drawings of the process connections
Certificates and approvals
Classification according to the pressure
equipment directive
(DGRL 97/23/EC)
For gases of fluid group 1 and
liquids of fluid group 1; fulfills
the requirements according to
article 3, paragraph 3 (good
engineering practice)
Protection against explosion 7MF1567-xxxx1-xxxx
Intrinsic safety "i" (with current
output only)
II 1/2 G Ex ia IIC T4 Ga/Gb
II 1/2 D Ex ia IIIC T125ÀC Da/Db
EC type examination certificate SEV 10 ATEX 0146
Connection to certified intrinsi-
cally safe resistive circuits with
maximum values
U
i
< 30 VDC; I
i
< 100 mA; P
i
< 0.75 W
Effective internal inductance and
capacitance for versions with plugs
complying with EN 175301-803-A
and M12
L
i
= 0 nH; C
i
= 0 nF
SITRANS P220, type 7MF1567
Additional notes on installation
The following conditions relating to types
7MF1567-***01-1**1 7MF1567-***01-2**1 7MF1567-***01-5**1
must be met:
Operation is permitted only when connected to certified intrinsically-safe resistive
circuits with the following maximum values:
U
i
< 30 V
I
i
ª < 100 mA
P
i
ª < 750 mW
Internal inductance Li = 0 nH
Internal capacitance Ci = 0 nF
A maximum ambient air temperature T
a
of -25 to +85 ÀC is permitted for the pressure transmitter.
Use as a resource belonging to category 1/2:
The pressure transmitters can be mounted in the wall separating the area with category 1 requirements (zone 0) and the area with category 2 requirements (zone 1).
In this case, the process connection must be adequately sealed in compliance with EN 60079-26, clause 4.6, for example by providing degree of protection IP67 in
compliance with EN 60529. The supply must be via intrinsically safe circuits with type of protection ia. The measuring cell may only be used for flammable materials
to which the diaphragms of the measuring cells are adequately resistant both chemically and in terms of corrosion.
7/16„-20 UNF
G1/2„
30.230.2
50.5
10.7
25.5
M16x1.5
or
1/2-14 NPT
± 24
36
max. 30 Nm
max. 20 Nm
max. 20 Nm
max. 20 Nm
M12x1 / Fixcon
2)
Agreement with DIN EN 60062
3)
The letter G is not permitted for new applications since it deviates from
DIN EN 60062. It serves only for coding back.
(1)
Decoding for year, month and day information
Code
(2)
1 2 3 4 5 6 7 8 9 O N D
Month January February March April May June July August September October November December
Code
(2)
A B C D I F H (G)
(3)
J K L M N P R S T U V W X
Calendar year 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 2026 2027 2028 2029
Code 01 - 31
Day of month 1st to 31st day
The date of manufacture can be seen on the label of the pressure transmitter, for example: LKK-YMDD-XXX-XX-XXX
Manufacturer's abbreviation
Date as "year-month-day„
3 digits of the order number
Order position
Single part number
Separator
(1)
Technical support
You can contact Technical Support for all IA and DT products:
Via the Internet with the support request: www.siemens.com/automation/support-request
E-mail: support.automation@siemens.com
Phone: +49 (0) 911 895 7 222
Fax: +49 (0) 911 895 7 223
Further information about our technical support is available on the Internet at www.siemens.com/automation/csi/service
P
max
< 60 bar P
max
< 60 bar
SO_BA_1567_A5_EN_V2.indd 4SO_BA_1567_A5_EN_V2.indd 4 19.12.2011 11:06:5119.12.2011 11:06:51