Rated conditions
Degree of protection (to EN 60529)
IP65 with connector to EN 175301-803-A
IP67 with M12 connector
IP67 with cable
IP67 with fast-fit cable gland
Electromagnetic compatibility
To EN 61326-1
To EN 61326-2-3
To NAMUR NE21, only for ATEX devices and
with a max. measurement error of ≤ 1%
Construction
Weight Approx. 0.090 kg (0.198 lb)
Process connections Dimension drawings (Page 31)
Electrical connections
Connector to EN 175301-803-A Form A with cable inlet M16x1.5
or ½-14NPT or Pg 11
M12 connector
2 or 3-wire (0.5 mm
2
) cable (∅ ± 5.4 mm)
Fast-fit cable gland
Material of the wetted parts
Measuring cell
Stainless steel, Mat. No. 1.4016
Process connection
Stainless steel, Mat. No. 1.4404 (SST 316 L)
Material of the non-wetted parts
Enclosure
Stainless steel, Mat. No. 1.4404 (SST 316 L)
Rack Plastic
CuZn, nickel-plated (M12 connector)
Cable
PVC spec.
Explosion protection 7MF1567-....1-....
Intrinsic safety "i" (only with current output)
II 1/2 G Ex ia IIC T4 Ga/Gb
II 1/2 D Ex ia IIIC T125 °C Da/Db
EC type-examination certificate SEV 10 ATEX 0146
Connection to certified intrinsically-safe resistive
circuits with maximum values
U
i
≤ 30 VDC; I
i
≤ 100 mA; P
i
≤ 0.75 W
Effective internal inductance and capacitance for
versions with connections to EN 175301-803-A
and M12
L
i
= 0 nH; C
i
= 0 nF
Technical specifications
SITRANS P220
Compact Operating Instructions, 02/2019, A5E03304437-AB 29