SITRANS P310 with HART
A5E35075329-01, 05/2015
35
Differential pressure and flow rate input
6 ... 600 mbar
0.660 kPa
2.409240.9 inH
2
O
0.016 ... 1.6 bar
1.6160 kPa
6.424642.4 inH
2
O
0.05 ... 5 bar
5 … 500 kPa
20.082008 inH
2
O
0.3 ... 30 bar
303000 kPa
4.35435 psi
Lower measuring limit
Measuring cell with silicone oil filling
-100 % of max. measuring range
(-33 % for measuring cell 30 bar/3000 kPa/435 psi) or
30 mbar a/3 kPa a/0.44 psi a)
Upper measuring limit
100% of maximum span
Start of scale value
Between the measuring limits (fully adjustable)
7.2
Output
Output
HART
Output signal
4 … 20 mA
Low saturation limit (fully adjustable)
3.55 mA, set to 3.84 mA in the factory
High saturation limit (fully adjustable)
23 mA, set to 20.5 mA or optionally 22.0 mA in the factory
Ripple (without HART communication)
I
SS
≤ 0.5 % of the max. output current
adjustable time constants damping coefficient
0 … 100 s, continuously adjustable
Adjustable time constants (T63) with local operation 0 … 100 s, in steps of 0.1 s
Factory-set to 2 s
Current transmitter
3.55 … 23 mA
Failure signal
3.55 … 23 mA
Load
Resistor R [Ω]
Without HART communication
U
H
Power supply in V
With HART communication
HART communicator (Handheld)
R =230 … 1100 Ω
SIMATIC PDM
R =230 … 500 Ω
Characteristic curve
Linearly increasing or linearly decreasing
Linear increase or decrease or root extraction increase
(only for P310 differential pressure and flow rate)