SITRANS P310 with HART
A5E35075329-01, 05/2015
35
Differential pressure and flow rate input
6 ... 600 mbar
0.6 … 60 kPa
2
0.016 ... 1.6 bar
1.6 … 160 kPa
2
0.05 ... 5 bar
5 … 500 kPa
2
0.3 ... 30 bar
30 … 3000 kPa
• Measuring cell with silicone oil filling
-100 % of max. measuring range
(-33 % for measuring cell 30 bar/3000 kPa/435 psi) or
30 mbar a/3 kPa a/0.44 psi a)
Between the measuring limits (fully adjustable)
• Low saturation limit (fully adjustable)
3.55 mA, set to 3.84 mA in the factory
• High saturation limit (fully adjustable)
23 mA, set to 20.5 mA or optionally 22.0 mA in the factory
• Ripple (without HART communication)
SS
≤ 0.5 % of the max. output current
adjustable time constants damping coefficient
0 … 100 s, continuously adjustable
Adjustable time constants (T63) with local operation 0 … 100 s, in steps of 0.1 s
• Current transmitter
• Failure signal
• Without HART communication
• With HART communication
HART communicator (Handheld)
Characteristic curve
• Linearly increasing or linearly decreasing
• Linear increase or decrease or root extraction increase
(only for P310 differential pressure and flow rate)