A5E32337695 SITRANS Probe LU (HART) – OPERATING INSTRUCTIONS Page 21
Operation
Accessing a parameter
1. Press PROGRAM then DISPLAY to
activate PROGRAM mode.
2. Either use the ARROW keys to scroll to
a different parameter, or
3. Press DISPLAY
to open the Parameter
Number field.
4. Key in the desired parameter number followed by
ENTER .
For example: press
.
The LCD displays the new parameter number and
value.
Changing a Parameter Value
1. Use the ARROW keys to scroll to the parameter number, or press
DISPLAY and key in the parameter number followed by ENTER .
2. Key in the new value.
3. Press ENTER to set the value.
Parameter Reset to Factory Default
1. Scroll to the parameter or enter its address.
2. Press CLEAR
then ENTER
. The value returns to the default setting.
Note:
• The following instructions apply when using the Handheld Programmer.
• Do not use the Handheld Programmer at the same time as SIMATIC PDM, or erratic
operation may result.
• You do not need to key in initial zeros when entering a parameter number: for
example, for P005, key in 5.
Notes:
• Security must be disabled to enable programming: set P000 to the Unlocked Value
stored in P069. (For more details, see
P069 Unlocked value
on page 42.)
• Invalid entries will be rejected or limited.
• CLEAR can be used to clear the field