A5E32337695 SITRANS Probe LU (HART) – OPERATING INSTRUCTIONS Page 23
Operation
Setup Instructions
Using the handheld programmer, set each parameter value to suit your application. (For
detailed instructions on accessing a parameter and changing the value, see page21.)
1. Select a language (P010: Language)
If a language is selected, parameter titles for parameters P010 to P001 are displayed in
the auxiliary reading field.
2. Select the measurement mode required for the application (P001:
Operation)
To measure how full the vessel is, select Level: the reading can be returned as level or as
volume (or flow – seeP050 on page 35 for details):
• for a level reading, ensure P050 is set to 0: the reading returns the distance from
process empty level (Empty) to the current level
• for a volume reading, select a vessel shape at P050, and set volume parameters
051 to 055 as required
Notes:
• The following instructions apply when using the Handheld Programmer.
•In PROGRAM mode, you can use the ARROW keys to scroll to a
parameter number.
• The default parameter values are indicated by an asterisk (*) in the tables.
Values
0*Numeric/None
1 English
2 German
3 French
4 Spanish
Parameter Auxiliary reading
P000
LOCK
P001
OPERATION
P002
MATERIAL
P003
MEAS RESP
P005
UNITS
P006
EMPTY
P007
SPAN
P010
LANGUAGE
Values
1*
Level returns material level referenced from Empty (process empty level).
The reading is returned in volumetric units if parameters 050 to 055 are
set to enable this.
2Space returns material level referenced from Span (process full level).
3
Distance returns material level referenced from the transducer face.