A5E32337695 SITRANS Probe LU (HART) – OPERATING INSTRUCTIONS Page 29
Parameters
Parameter Reference
SITRANS Probe LU is configured through its parameters, and the application determines
the parameter values which are entered into the instrument.
Please check your value entries carefully before operating SITRANS Probe LU, to ensure
optimum performance.
Helpful Hints
• Primary index is an address: for example, P054.
• Secondary index is a sub-address that allows for multiple values on an indexed
point, and allows indexed values from more than one parameter to be linked, for
example, the breakpoints in P054 and P055. (See pages 37 and 40 for more details.)
To access a parameter and change a value (primary index):
1. Press PROGRAM then DISPLAY to activate PROGRAM Mode.
2. Either use the ARROW keys to scroll to each parameter number, or
press DISPLAY again to access the parameter number field, and key in the
parameter number followed by ENTER .
3. Key in the new value.
4. Press ENTER .
Notes:
• Keep infrared devices such as laptops, cell phones, and PDAs, away from
SITRANS Probe LU to prevent inadvertent operation.
• Do not use the Handheld Programmer at the same time as SIMATIC PDM, or erratic
operation may result.
• The following instructions apply when using the Handheld Programmer.
•Press PROGRAM
then DISPLAY to access PROGRAM mode, and press
PROGRAM to return to RUN mode.
• CLEAR can be used to clear the field
• Default values (Factory settings) are indicated by an asterisk (*) in the parameter
tables, unless explicitly described.
Note: Initial zeros in a parameter number do not have to be entered: for example, for
P001, key in 1.