A5E32337695 SITRANS Probe LU (HART) – OPERATING INSTRUCTIONS Page 33
Parameters
P005 Units
Specifies measurement units used for dimensional values.
P006 Empty (process empty level)
Sets the distance from the transducer face to the process empty level, in units selected at
P005.
Enter the distance from the transducer face
to Empty (process empty level), using units
set in P005. Empty can be set to any
distance: not necessarily the bottom of the
vessel
P007 Span (process full level)
Sets the range to be measured (referenced from Empty) in units selected at P005.
Enter the distance between Empty (process empty level) and Span (process full level), in
units set in P005. Span can be set at any distance above Empty level.
1
Values
1*meters
2
centimeters
3
millimeters
4
feet
5
inches
Values
Range
(depends
on model
0.0000 to 6.10 m (20.01 ft)
or
0.0000 to 12.20 m (40.02 ft)
Default
Max. range:
6.10 m (20.01 ft) or
12.20 m (40.02 ft)
Notes:
• Default setting is maximum range.
• P006 and P007 are interlinked: see note
attached to P007.
Values
Range
(depends on model)
0.0000 to 6.00 m (20 ft) or
0.0000 to 12 m (40 ft)
Default
5.725 m (18.78 ft) or
11.725 m (38.47 ft)
See note on next page for more details.