A5E32337695 SITRANS Probe LU (HART) – OPERATING INSTRUCTIONS Page 35
Parameters
P050 Vessel (or Channel) Shape
Defines the vessel (or open channel) shape (see chart on next page) and allows
SITRANS Probe LU to calculate volume or flow instead of level. The default setting for
P050 is 0 (volume calculation not required).
Enter the value for the vessel shape matching the monitored vessel or reservoir (see
chart on page 36).
P051 Maximum Volume
For readings in volumetric units instead of percentage values, enter the vessel volume
corresponding to Span (P007). Any volumetric units can be chosen, because the volume
calculation is based on the maximum volume, and scaled according to the Vessel Shape
(P050) value. If no value is entered, the default is 100, and the reading will be a
percentage value.
Enter the vessel volume corresponding to Span (P007).
1. Key in the value. (For example, if maximum volume = 3650 m
3
, key in 3650.)
2. Press ENTER .
If the value is too large for the LCD display, enter larger units.
Example:
If maximum volume = 267,500 gallons, key in 267.5 (thousands of gallons).).
Values
Range 0.0000 to 99999
Default 100.0
Related Parameters
P006 Empty
P007 Span