A5E32337695 SITRANS Probe LU (HART) – OPERATING INSTRUCTIONS Page 55
Parameters
P713 Echo Lock Window
Adjusts the size of the Echo Lock Window. This value is automatically altered when
Measurement Response (P003), Maximum Fill Rate (P700), or Maximum Empty Rate
(P701), are altered.
The Echo Lock Window is a ’distance window
1
, centered on the echo used to derive the
reading. When a new measurement falls within the window, the window is re-centered
and the new reading calculated. Otherwise, the new measurement is verified by Echo
Lock (P711) before the reading is updated. The distance value of this parameter is given
for a temperature of 20
o
C (68
o
F).
When the value is 0, the window is automatically calculated after each measurement.
The value is fixed at 0 if Echo Lock (P711) is set to 3.
• For slower Measurement Response values (P003), the window is narrow.
• For faster P003 values the window becomes progressively wider.
P752 HART address
Sets the device address or poll ID on a HART network. Any address other than 0 will
cause the output current to be a fixed value, and the current will not indicate the reading.
Values
Range 0.000 to 9999
Default 0.000
Altered by
P003 Measurement Response
Related Parameters
P005 Units
P711 Echo Lock
1.
Units are those set in P005.
Note: The echo lock window is stored as standard samples, but displayed in units
based on P005. Any value entered for P713 will be rounded to the nearest sample.
Note: Accessible via the handheld programmer only by keying in P752.
Values Range 0 to 15