Page 58 SITRANS Probe LU (HART) – OPERATING INSTRUCTIONS A5E32337695
Parameters
P805 Echo Confidence
Measures echo reliability. It displays the echo confidence of the measurement echo from
the last shot. P804 defines the minimum criterion for echo confidence.
Press the measurement key
to get a new reading that will update confidence
values.
Both short and long shot Echo Confidence values are displayed.
P806 Echo Strength
Displays the absolute strength (in dB above 1 μV rms) of the echo selected as the
measurement echo.
Press the measurement key
to get a new reading that will update echo strength.
Values (view only)
Format
x:y
x = short (range 0 to 99)
y = long (range 0 to 99)
---- (Shot not used)
Related Parameters
P804 Confidence Threshold
P830 TVT Type
Display Description
x : -- short shot confidence value, (long shot not used)
-- : y long shot confidence value, (short shot not used)
x : y short and long shot confidence values (both used)
E transducer cable is open or short circuited
-- : -- no shots were processed for Sonic Intelligence evaluation
Values (view only)
Display –20 to 112