Page 66 SITRANS Probe LU (HART) – OPERATING INSTRUCTIONS A5E32337695
Parameters
P923 Distance Measurement
Displays the distance between the monitored surface and the transducer face.
P924 Volume (or Flow) Measurement
The calculated vessel capacity in Maximum Volume (P051) or percent of Maximum
Volume (volume calculation must be enabled at P050).
P999 Master Reset
Resets all parameters to their factory settings, with the following exceptions:
• P000 and P069 are not reset.
• The learned TVT curve is not lost.
Use this feature after upgrading software:
1. Select P999.
2. Press CLEAR
then ENTER
to Clear All and initiate reset.
3. Reset complete.
(Note: Reset takes several
seconds to complete.)
Values (view only)
Range –99999 to 99999
Values (view only)
Range : –99999 to 99999
- - - -
Display when volume calculation is not
enabled at P050 (P050 = 0)
Related Parameters
P051 Maximum Volume
P050 Vessel (or Channel) Shape
Note: Following a Master Reset, complete reprogramming is required.