Page 94 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02
mmmmm
H: Parameters
2.7.7.8. Range (Auto False Echo Suppression Distance)
1
: (default 1)
Defines the endpoint of the Learned TVT distance.
a. Go to Input > Detailed Setup > TVT setup > Distance.
b. Determine the actual distance from the reference point (transducer
face) to the material surface.
c. Subtract 0.5 m (20") from this distance, and enter the result.
2.7.7.9. Shaper Mode (default Off)
Turns TVT Shaper on or off. (For use only by Siemens personnel.)
1.
This parameter cannot be reset to the factory default.
Display before Auto False Echo Suppression
default TVT
curve
TVT
Hover Level
false
echo
true
echo
Distance (meters)
Level (db)
Display after Auto False Echo Suppression
TVT curve
(learned)
material
level
false
echo
Distance (meters)
Level (db)