Explosion protection
5.2 FM
SITRANS SL
86 Operating Instructions, 12/2010, A5E01132948-04
Example: Digital out 0
,
PHDV
5
ORDG
&XVWRPHUVLGH
!6,75$166/
9
Figure 5-14 Using digital output
V
0
can be maximum 30 V DC.
R
load
must be minimum 60 Ω (max. 0.5 A in the relay).
Example: Analog out 0
!6,75$166/
9

&XVWRPHUVLGH
,
PHDV
5
ORDG
Figure 5-15 Using analog output
V
0
must be minimum 7.5 V DC and maximum 30 V DC.
R
load
can be maximum ((V
0
– 7.5 V)/0.025 A) Ω.
Note
SITRANS SL provides no supply voltage for the analyzer outputs, i.e. the analog outputs
of the SITRANS SL are passive and thus must be powered externally!