5
Siemens A6V12681516_enUS_a
Smart Infrastructure 10/12/2022
Observe permissible temperatures (see "Technical data [ 9]").
Mounting
WARNING
Do not use pipe wrenches, pliers or similar tools.
Avoid lateral pressure or (cable) tension on the mounted actuator!
Valve and actuator are easy to assemble on site before commissioning:
Remove protective cover from the valve body.
Position the actuator and tighten the union nut manually.
See "Mounting instructions" for graphical instructions.
Orientation
Commissioning
When commissioning, check both wiring and functioning of the actuator.
Actuator stem extends Normally open valve closes, normally closed valve opens
Actuator stem retracts Normally open valve opens, normally closed valve closes
NOTICE
The actuator must be commissioned only with a correctly mounted valve in place!
Self-calibration
When operating voltage is applied, the actuator self-calibrates (fully retracted fully
extended setpoint).
Power
On
Calibration
Y
t
Fully retracted
Fully extended