6
Siemens
A6V13359035_en--_b
Smart Infrastructure
2023-05-16
CAUTION
Never intervene manually during self-calibration.
NOTICE
Correct calibration is only possible with valve stroke > 1.2 mm. Valve stroke < 1.2 mm
results in calibration failure.
If calibration fails, the actuator performs another calibration automatically after
10 seconds.
After three failed calibration attempts, the actuator stem remains in the extended
position and the valves are open.
Power
On
Calibration
Y
t
Fully retracted
Fully extended