Orientation
Commissioning
When commissioning, check both wiring and functioning of the actuator.
Normally open valve closes, normally closed
valve opens
Normally open valve opens, normally closed
valve closes
The actuator must be commissioned only with a correctly mounted valve in place!
Self-calibration
When operating voltage is applied, the actuator self-calibrates (fully retracted ➙ fully
extended ➙ setpoint).
Never intervene manually during self-calibration.
● Correct calibration is only possible with valve stroke > 0.05 inch (1.2 mm). Valve stroke
< 1.2 mm results in calibration failure.
● If calibration fails, the actuator performs another calibration automatically after
10 seconds.
● After three failed calibration attempts, the actuator stem remains in the extended
position and the valves are open.
Manual operation
A 3-mm hexagonal wrench can be used to move the actuator to any position.
Power
On
Calibration
Y
t
Fully retracted
Fully extended