9.2.7.3 Troubleshooting
When you leave the commissioning menu, the universal controller checks whether
the room and the supply air temperature sensor are connected and then responds
as follows:
Room and supply air
temperature sensor
present?
If, at that time, the measured values of room and supply air temperature are
available, but are missing later, a sensor error message is delivered and
presented on the display:
"Xx ---" => sensor missing
"Xx ooo" => short-circuit
If, at that time, the measured value of the room temperature is missing, the
supply air is controlled to the adjusted room temperature setpoints
If, at that time, the measured value of the supply air temperature is missing, the
plant will be shut down (MAINALM)
9.2.7.4 Settings
Path: … > COMMIS > CONF > CTLOOP 1
Configuration
Display Name Setting
STRATGY Control strategy CAS
Path: … > PARA > CTLOOP 1
Setting values
Display Name Range Factory setting
ROOM XP Room influence Xp 1…1000 K 10 K
ROOM TN Room influence Tn 00.00…60.00 m.s 10.00 m.s
SU MAX Supply air limit
value max
50…+250 °C 35 °C
SU MIN Supply air limit
value min
50…+250 °C 16 °C
SU DMIN Min limitation supply
air delta
0…50 K 50 K
SU DMAX Max limitation
supply air delta
0…50 K 50 K
100 / 174
Siemens Universal Controllers RLU2… CE1P3101en
Building Technologies Controller (CTLOOP x) 29.08.2008