9.6.4 Troubleshooting
When you leave the commissioning menu, the universal controller checks whether
a sensor is connected to the LIM input.
Limit sensor
connected?
• If, at that time, a sensor is connected, but is missing later, a sensor error
message is delivered and presented on the display:
– "Xx ---" => sensor missing
– "Xx ooo" => short-circuit
• If, at that time, no sensor is connected, limitation will be deactivated
9.6.5 Settings
Path: … > COMMIS > CONF > CTLOOP 1 (type A)
Configuration
Display Name Range / comments
STRATGY Control strategy LIM (only type A)
Path: … > COMMIS > CONF > CTLOOP 1 (type U)
Display Name Range / comments
LIM General limit
controller
Activation of general limitation; adjustable
values: ---, X1, X2, … (nur analoge Werte)
(nur Typ U)
Path: … > COMMIS > CONF > CTLOOP 2
Display Name Range / comments
LIM General limit
controller
Activation of general limitation; adjustable
values: ---, X1, X2, … (analog values only)
Path: … > PARA > CTLOOP 1
Setting values
… > PARA > CTLOOP 2
Display Name Range Factory setting
LIM MAX Gen limiter limit
value high
Limit sensor input
range
35 °C
LIM MIN Gen limiter limit
value low
Limit sensor input
range
16 °C
LIM DHI Gen limiter
differential high
0…500 K 50 K
LIM DLO Gen limiter
differential low
0…500 K 50 K
LIMCOOL Reduction min
limitation cooling
0…10 K 0 K
LIM XP Gen limiter P-band
Xp
0…500 K 15 K
LIM TN Gen limiter integr
action time Tn
00.00…60.00 m.s 02.00 m.s
123 / 174
Siemens Universal Controllers RLU2… CE1P3101en
Building Technologies Controller (CTLOOP x) 29.08.2008