9.7.3 Troubleshooting
When you leave the commissioning menu, the universal controller checks whether
a sensor is connected.
Sensor connected?
• If, at that time, the sensor is connected, but is missing later, or if there is a short-
circuit in the cable, a sensor error message is delivered and presented on the
display:
– "Xx ---" => sensor missing
– "Xx ooo" => short-circuit
• If, at that time, the sensor is not connected, limitation will be deactivated
9.7.4 Settings
Path: … > COMMIS > CONF > CTLOOP 1
Configuration
… > COMMIS > CONF > CTLOOP 2
Display Name Range / comments
SEQLIM Sequence limit controller Activation of limitation of individual
sequence; adjustable values:
---, X1, X2, … (analog values only)
Path: … > PARA > CTLOOP 1
Setting values
… > PARA > CTLOOP 2
Display Name Range Factory setting
SEQ MOD Type of limitation Min, max Min
SEQ SEL Sequence selection Seq1, Seq2, Seq4,
Seq5
Seq1
SEQ SET Limit value Input signal range 1 °C
SEQ XP Seq limiter P-band Xp Input signal range 10 K
SEQ TN Seq limiter integr action time
Tn
00.00…60.00 m.s 01.00 m.s