9.9.3 Troubleshooting
If there is no outside temperature sensor signal, the controller does not shift the
setpoint.
OT sensor signal
available?
9.9.4 Settings
Path: … > PARA > CTLOOP 1
Setting values
Display Name Range Factory
setting
SUM-D Summer compensation
delta
0…+50 K 0 K
SUM-END Summer compensation
end
SUM-STT…50 °C 30 °C
SUM-STT Summer compensation
start
WIN-STT…SUM-END 20 °C
WIN-STT Winter compensation start WIN-END...SUM-STT 0 °C
WIN-END Winter compensation end −50 °C…WIN-STT −10 °C
WIN-D Winter compensation delta −50…+50 K 0 K
130 / 174
Siemens Universal Controllers RLU2… CE1P3101en
Building Technologies Controller (CTLOOP x) 29.08.2008