10.3.3 2-stage frost protection on the air side (DC 0…10 V)
This picture shows an application with 2-stage, air-side frost protection:
Application example
3101S23
T
AI
X1
x
Y
SIGNAL Y
LABEL
FRST
Reliable frost protection depends on correct sensor placement!
Note
If the temperature falls below the set starting point (= limit value + 2 K + P-band),
the following actions are triggered:
Temperature drops
below starting point
All heating sequences are steplessly opened and all cooling sequences are
steplessly closed
The air heating coil pump is switched on
The purpose is to prevent the temperature from falling below the "frost hazard" limit
value (SET-ON).
If the temperature still drops below the above limit value, the following actions are
triggered:
Actions if temperature
drops below limit value
The fan release relay is deenergized (no release of fan)
The control loop configured with the air heating coil at risk from frost switches off
all cooling sequences, and opens all heating sequences to 100%. It also
switches the air heating coil pump on.
=> Important: Step switches are switched on as well!
If 2 controllers are configured in the RLU2…, the second (other) control loop is
switched off as well
The outside air dampers are closed
139 / 174
Siemens Universal Controllers RLU2… CE1P3101en
Building Technologies Frost protection (FROST) 29.08.2008