4.2.2 Start from main menu
The COMMIS (commissioning) menu is only active at the password level
(password = 2). If the password level is not already selected, simultaneously press
the ESC and OK buttons to activate it.
Prerequisite
When a user enters the commissioning menu from the main menu, the controller
indicates that the plant will be stopped:
Plant is stopped
COMMIS
PASS
Pressing the OK button produces the following results:
• The controller stops the plant and deactivates the control process
• All outputs are set to a defined OFF state
• It also deactivates all of the controller's internal safety features!
• The submenus of COMMIS (commissioning) appear, the first menu PARA blinks
24 / 174
Siemens Universal Controllers RLU2… CE1P3101en
Building Technologies Commissioning 29.08.2008