7.2.8 Settings
Path: … > COMMIS > CONF > X1…X5
Configuration
Display Name Range / comments
LABEL Input identifier Assignment of ROOM, OUTS, SAT,
TEMP, %, 0.0, 0000
SIGNALY Measured value signal output Output of passive temperature
sensor as active signal
Path: … > PARA > X1…X5
Setting values
Display Name Range Factory setting
TYPE Type NI, 2XNI, T1, PT, 0-10 NI
MIN VAL Value low −50…+500 (with analog
signals only)
-50
MAX VAL Value high −50…+500 (with analog
signals only)
250
CORR Correction −3.0…+3.0 (with °C only) 0 K
Path: INFO
Display values
Display Name Comments
X1 X1 Display of current measured value at terminal X1
… … …
X5 X5 Display of current measured value at terminal X5
Path: … > COMMIS > TEST
Wiring test
Display Name Positions
X1 X1 Display of current measured value at terminal X1,
non-adjustable
… … …
X5 X5 Display of current measured value at terminal X5,
non-adjustable
Display Name Effect
Xx --- / ooo Sensor error
Xx…
Non-urgent message; plant not stopped.
However, if sensor is used for the main controlled
variable: Plant stopped
Fault status messages
43 / 174
Siemens Universal Controllers RLU2… CE1P3101en
Building Technologies Inputs 29.08.2008